Submersible pump cable size: flat cable chart by HP and length for borewells in Kishanganj, Purnea and Katihar
Submersible pump cable size depends on pump HP and length: 1.5–2.5 sq mm flat cable for short runs, 4–10 sq mm for deep or long runs to cut voltage drop.
Submersible pump cable size depends on two things: the pump’s current (its HP and whether it is single-phase or three-phase) and the total cable length from the starter to the pump. For a short run, 1.5 or 2.5 sq mm 3 core flat copper cable is enough for most small pumps; for long or deep runs you go up to 4, 6 or 10 sq mm so the voltage drop stays low and the motor does not overheat. Use the chart below as a starting point, then match it to the pump maker’s manual.
This guide is for pump installers, borewell and boring contractors, electricians, farm owners and apartment builders in Kishanganj, Purnea, Katihar and Araria. The same advice applies across North Bengal, Bihar and Sikkim.
What is submersible flat cable and which standard should it have?
Submersible pump cable is a 3 core flat cable: three copper cores laid side by side (usually red, yellow and blue) inside a tough black sheath. It is flat so that it lies close to the pipe column inside a narrow borewell.
- Standard: look for IS 694 marking. Havells, for example, describes its flat cable as “three core flat PVC insulated industrial grade cable for submersible use, 1.1 kV as per IS:694” (Havells).
- Conductor: fine, flexible annealed copper strands. RR Kabel lists Class 5 (flexible) copper for its PVC flat cable (RR Kabel PVC flat cable).
- Voltage grade: 1.1 kV (1100 V) grade.
- Packing: commonly 100 metre coils, with longer lengths on request from the maker.
Avoid unmarked flat cable: under-size copper looks the same outside but heats up and drops voltage.
What size cable for a submersible pump? (HP vs length chart)
The chart below is our worked guide, not a manufacturer’s table. We calculated it for about 3% voltage drop, using the conductor resistance values RR Kabel publishes for PVC flat cable, typical full-load current for each pump size, and some margin for the cable running warm. “Length” is the full one-way cable length: borewell depth to the pump, plus the run from the borewell to the starter.
Three-phase pumps (415 V)
| Pump size | Typical current (approx.) | Up to 50 m | Up to 100 m | Up to 150 m | Up to 200 m |
|---|---|---|---|---|---|
| 3 HP | 5 A | 1.5 sq mm | 2.5 sq mm | 4 sq mm | 4 sq mm |
| 5 HP | 7.5 A | 1.5 sq mm | 4 sq mm | 4 sq mm | 6 sq mm |
| 7.5 HP | 11 A | 2.5 sq mm | 4 sq mm | 6 sq mm | 10 sq mm |
| 10 HP | 14–15 A | 4 sq mm | 6 sq mm | 10 sq mm | 10 sq mm |
| 15 HP | 21 A | 4 sq mm | 10 sq mm | 16 sq mm | 16 sq mm |
| 20 HP | 28 A | 6 sq mm | 10 sq mm | 16 sq mm | 25 sq mm |
Single-phase pumps (230 V)
| Pump size | Typical current (approx.) | Up to 50 m | Up to 100 m | Up to 150 m |
|---|---|---|---|---|
| 0.5 HP | 4 A | 1.5 sq mm | 4 sq mm | 4 sq mm |
| 1 HP | 7 A | 2.5 sq mm | 6 sq mm | 10 sq mm |
| 1.5 HP | 10 A | 4 sq mm | 10 sq mm | 10 sq mm |
Motor currents differ by brand and model. Read the amps on the pump nameplate, and if the pump maker gives a cable chart, follow it. When in doubt, go one size up; it costs far less than a burnt winding.
Why does a long cable burn the pump motor? On a long run, part of the voltage is lost in the cable before it reaches the motor. A motor on low voltage draws more current, runs hot and loses life. At the end of a long rural line, where voltage is already low, a thin cable makes it worse.
So on long runs, voltage drop decides the size, not just the amps. That is why a 10 HP pump fine on 4 sq mm at 50 m needs 10 sq mm at 150 m.
PVC or XLPE flat cable: which one should I buy?
| Point | PVC flat cable | XLPE flat cable |
|---|---|---|
| Insulation | PVC (also available as PVC HR 85°C) | XLPE |
| Current it can carry | Lower for the same size | Higher for the same size |
| Common use | Most farm and domestic borewells | Bigger pumps, hot water, heavy-duty and industrial use |
| Price | Lower | Higher |
As an example of the difference, RR Kabel’s published rating for 2.5 sq mm is 22 A for its PVC flat cable and 30 A for its XLPE flat cable (RR Kabel XLPE flat cable). Remember, though: on long runs the voltage drop chart above still decides the size, whichever insulation you pick.
How do I calculate the total cable length for a borewell?
Measure it in three parts and add a little extra:
- Pump setting depth – how far down the pump will hang (not the full bore depth).
- Surface run – borewell head to the starter panel, following the actual route.
- Spare – a few metres for the joint, the starter connection and a drip loop.
Too short means an extra joint inside the bore, a weak point. Too long is wasted money. Tell us the exact length and we cut it.
Can I join submersible cable, and what about the surface run?
- Joint at the pump lead: use a proper submersible cable jointing kit (heat-shrink or resin type) so no water reaches the copper. Tape alone is not enough under water.
- Avoid joints mid-way down the bore. Buy one continuous length.
- Surface run to the starter: flat cable is made for inside the bore. Where the cable crosses open ground, a field or a path, run it in pipe or use an armoured cable for that stretch. Our armoured vs unarmoured cable guide explains when armour is worth it.
- Flood areas: in the Seemanchal belt the monsoon can flood fields. Keep the starter and joints above the high-water mark.
- Protection: the pump needs the right starter with an overload relay and correct earthing. For three-phase pumps, see DOL vs star delta starter. Get the wiring done by a licensed electrician.
What should a contractor write in the BOQ for pump cable?
For tenders, PHED or irrigation works, apartment projects and farm jobs, a clear spec avoids wrong supply:
| Item | What to specify |
|---|---|
| Cable type | 3 core flat submersible cable, copper conductor |
| Standard | IS 694, ISI marked |
| Voltage grade | 1.1 kV |
| Insulation | PVC / PVC HR 85°C / XLPE (state which) |
| Size | sq mm per pump (from current and length) |
| Length | Cut length per borewell, or 100 m coils |
| Brand | Approved make list (e.g. Havells, Polycab, KEI, RR Kabel) |
| Accessories | Jointing kit, lugs, starter, earthing |
For many borewells, list each one with pump HP, depth and surface run so the quote and dispatch are easy to check.
What decides submersible cable price?
We don’t quote prices on the blog because copper rates move often. The price of flat cable depends on:
- Size (sq mm) – more copper, higher price.
- Insulation – XLPE and HR grades cost more than standard PVC.
- Brand and its current price list.
- Quantity – full coils vs cut lengths.
- Copper rate on the day of billing.
WhatsApp us for today’s rate on the size and brand you need.
Shree Shyam Suppliers in Siliguri is an authorised dealer for Havells, Lauritz Knudsen (L&T) and Mescab, and we also deal in Polycab, KEI and RR Kabel cables. You get genuine ISI-marked cable, help choosing the right size for the pump and depth, cable cut to length and an itemised quote. Starters, MCBs, earthing material and jointing items come from the same counter, so one order covers the whole pump job. See our full range of cables and wires.
Ordering tip
Send us on WhatsApp: pump HP, single-phase or three-phase, pump setting depth, distance from borewell to starter, number of borewells, preferred brand and PVC or XLPE. Add your site location (for example Kishanganj, Purnea, Katihar or Araria). Shree Shyam Suppliers will reply with the right cable size for each pump and an itemised quote.
Quick answers
Which cable is used for a submersible pump?
A 3 core flat copper submersible cable, 1.1 kV grade, made to IS 694 and ISI marked. It is flat so it lies close to the pipe inside the borewell.
What size cable for a 1 HP submersible pump?
For a single-phase 1 HP pump, 2.5 sq mm flat cable is usually enough up to about 50 m of total cable length; use 6 sq mm up to about 100 m. Check the pump nameplate current and the maker's chart.
What size cable for a 5 HP three-phase submersible pump?
As a general guide, 1.5 sq mm up to about 50 m, 4 sq mm up to about 150 m and 6 sq mm up to about 200 m of cable length. Go one size up if the supply voltage is low.
Is XLPE flat cable better than PVC flat cable?
XLPE flat cable carries more current for the same size and handles heat better, so it suits bigger or heavy-duty pumps. PVC flat cable is fine and cheaper for most farm and domestic borewells.
Can I join submersible cable inside the borewell?
Avoid joints mid-way down the bore and buy one continuous length. At the pump lead, use a proper submersible jointing kit, not just tape.
See the products: Cables & wires