MCCB rating for load: how to select MCCB size and kA for hotels and buildings in Gangtok, Namchi and Rangpo
MCCB rating for load: work out full-load current (about 1.5 A per kW on 3-phase), add 25%, pick the next size up and match kA to the fault level.
To pick the right MCCB rating for a load, first work out the full-load current (on a 415 V three-phase supply that is roughly 1.5 A for every kW at 0.9 power factor), add about 25% margin, and choose the next standard MCCB size above that. Then check two more things: the breaking capacity (kA) must be higher than the fault level at that point, and the cable connected to it must be able to carry the MCCB’s set current.
This guide is written for electrical contractors, consultants and site engineers working on hotels, homestays, hospitals, offices and project sites in Gangtok, Namchi and Rangpo. The same method applies across North Bengal, Bihar and Sikkim.
How do I calculate MCCB size from kW load?
Use this simple formula for a balanced three-phase load:
Current (A) = kW × 1000 ÷ (1.732 × 415 × power factor)
At 0.9 power factor this works out to about 1.55 A per kW. At 0.8 power factor it is about 1.74 A per kW, so motor-heavy loads need a bigger breaker for the same kW.
Then:
- Add the connected load of the feeder or building, and apply a realistic diversity factor (not every load runs at once). Your consultant or the approved drawing usually gives this.
- Work out the full-load current with the formula above.
- Multiply by 1.25 for margin. This is common trade practice, not a fixed rule; follow the design if it says otherwise.
- Pick the next standard MCCB frame and set its thermal release close to the needed current.
MCCB rating chart for common loads
The chart below uses 415 V, 0.9 power factor and a 25% margin. It is a quick-check guide based on general practice. Always go by the electrical design for the final rating.
| Load (kW, 3-phase) | Full-load current (approx.) | With 25% margin | Usual MCCB rating |
|---|---|---|---|
| 20 kW | 31 A | 39 A | 40 A |
| 30 kW | 46 A | 58 A | 63 A |
| 40 kW | 62 A | 77 A | 80 A |
| 50 kW | 77 A | 97 A | 100 A |
| 75 kW | 116 A | 145 A | 160 A |
| 100 kW | 155 A | 193 A | 200 A |
| 150 kW | 232 A | 290 A | 320 A (or 400 A frame, set lower) |
| 200 kW | 309 A | 386 A | 400 A |
| 300 kW | 464 A | 580 A | 630 A |
Standard MCCB ratings you will see in catalogues include 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160, 200, 250, 320/400, 500, 630 and 800 A. MCCBs are also made in bigger sizes, but large incomers of roughly 800 A and above often use an ACB instead.
What kA breaking capacity MCCB do I need?
Breaking capacity is how much fault (short-circuit) current the MCCB can safely break. If the fault level at the panel is higher than the MCCB’s kA, the breaker can fail during a short circuit. That is dangerous.
Two numbers appear on the MCCB:
- Icu – ultimate breaking capacity. It must be more than the prospective fault current at that point.
- Ics – service breaking capacity, shown as a percentage of Icu. A higher Ics means the breaker is fit to keep working after clearing a fault. For main incomers in hotels and hospitals, ask for Ics = 100% of Icu where the budget allows.
As a rough idea, the fault level close to a transformer depends on its size and impedance:
| Transformer | Full-load current (approx.) | Fault level near transformer (approx.) | Typical MCCB/ACB kA asked |
|---|---|---|---|
| 250 kVA | 333 A | about 8 kA | 25 kA |
| 500 kVA | 667 A | about 15 kA | 25–36 kA |
| 1000 kVA | 1,333 A | about 27 kA | 36–50 kA |
These figures assume 4–5% transformer impedance and are general practice only. The real fault level depends on the transformer, cable lengths and the utility supply, so the designer should confirm it. Sub-DBs far from the main panel see less fault current, so a lower kA MCCB is often fine there.
Thermal magnetic or microprocessor release MCCB — which one?
| Feature | Thermal magnetic (TM) MCCB | Microprocessor / electronic release MCCB |
|---|---|---|
| Usual use | Feeders, sub-DBs, small incomers | Main incomers, big feeders, DG incomers |
| Settings | Fixed or limited thermal adjustment | Wide adjustment of overload, short-time and instantaneous |
| Earth fault protection | Usually not built in | Often available as an option |
| Selectivity with downstream breakers | Basic | Easier to get proper discrimination |
| Cost | Lower | Higher |
For a hotel or hospital main incomer, an electronic release MCCB helps you set it to match the DG set and get discrimination with the floor DBs, so one fault does not black out the whole building. For a 63 A or 100 A feeder to a floor DB, a thermal magnetic MCCB is usually enough.
3 pole or 4 pole MCCB for a hotel or building?
- 4 pole MCCB: common for the main incomer and DG incomer, especially where there is a changeover between mains and generator, and where single-phase loads make the neutral carry current. Switching the neutral avoids problems during changeover.
- 3 pole MCCB: common for motor feeders, pumps, lifts and balanced three-phase loads with no neutral.
Most hotels and homestays in Gangtok and Namchi run on mains with DG backup, so the incomer and changeover side need proper attention. Our guide on changeover switch for generator explains how to size the changeover with the MCCB.
Which cable size goes with my MCCB?
The MCCB protects the cable, so the cable’s current rating (after derating) must be equal to or more than the MCCB’s set current. A common site mistake is fitting a 200 A MCCB on a cable that can only carry about 150 A in that laying condition.
Points to check:
- Derate for grouping, ambient temperature and laying method (in ground, on tray, in pipe).
- Use the right lug size and, for aluminium cable on copper terminals, bimetallic lugs.
- Check the MCCB terminal can take the cable size or needs a spreader/extension.
For aluminium armoured cable ratings, see our aluminium armoured cable current rating chart.
What should a contractor mention in the BOQ for an MCCB?
A clear BOQ line saves back-and-forth and wrong supply. Mention:
- Rated current (In) and frame size, e.g. 250 A frame set at 200 A
- Number of poles: 3P or 4P
- Breaking capacity: Icu in kA at 415 V, and Ics if specified
- Release type: thermal magnetic or microprocessor, with or without earth fault
- Fixed or adjustable settings
- Accessories: rotary handle, shunt trip, undervoltage release, auxiliary contacts, spreaders, terminal covers
- Standard: MCCBs should conform to IS/IEC 60947-2
- Preferred brand, or “approved make” list from the consultant
Anything special for sites in the Sikkim hills?
- Altitude: MCCB ratings are usually given for sites up to 2,000 m. Gangtok, Namchi and Rangpo are below that, but for sites higher up in North Sikkim, ask for the maker’s altitude derating.
- Damp and condensation: use panels with proper gaskets and keep heaters or ventilation where the panel room stays damp through the monsoon.
- Lightning: the hills see heavy lightning. Pair the main MCCB with a surge protection device and good earthing, especially on a new hotel or block.
- Transport: big MCCBs and panels should be packed well for hill roads; tell us your site location in advance so the material is packed for the trip.
Installation, setting and testing of MCCBs should always be done by a licensed electrician or electrical contractor, as per the approved drawing.
Why buy MCCBs from an authorised dealer?
Shree Shyam Suppliers is an authorised dealer for Havells, Lauritz Knudsen (L&T) and Mescab, and we also deal in Siemens, Schneider, Legrand and other leading switchgear brands. Buying from a local authorised dealer means genuine stock with the maker’s warranty, help in matching the frame, kA and release to your BOQ, and one place for MCCBs, panels, cables, lugs and glands. Browse our switchgear range.
Ordering tip
Send Shree Shyam Suppliers your list on WhatsApp with: MCCB rating and frame, 3P or 4P, kA required, release type, accessories, brand or approved makes, quantity and site location. If you only have the load, send the kW and supply details and we will help you work out the rating. We will reply with an itemised quote and today’s rate.
Quick answers
Which MCCB for a 100 kW load?
A 100 kW three-phase load at 415 V and 0.9 power factor draws about 155 A. With a 25% margin that is about 193 A, so a 200 A MCCB is the usual choice, with the cable rated for at least the set current.
What is the difference between Icu and Ics in an MCCB?
Icu is the highest fault current the MCCB can break once. Ics is the fault current it can break and still stay fit for service, shown as a percentage of Icu. For main incomers in hotels and hospitals, ask for Ics equal to 100% of Icu.
Is 25 kA MCCB enough for a building?
For many sub-DBs and small buildings fed by a transformer of up to about 250 kVA, 25 kA is usually enough. Near a larger transformer the fault level can be higher, so the designer should confirm the fault level before you finalise the kA.
MCCB or ACB for main incomer?
MCCBs are common for incomers up to about 630 A. For larger incomers, roughly 800 A and above, an ACB is often used because it offers better settings and maintenance options. Follow the approved electrical design.
What is the MCCB price?
MCCB price depends on the rating, frame size, kA, number of poles, release type, accessories and brand. WhatsApp us the details for today's rate and an itemised quote.