Cable size for 3 phase motor: 4 sq mm copper armoured cable covers motors up to 15 HP on runs to 50 m; bigger motors and longer runs need 6 to 50 sq mm.

For a three-phase 415 V motor, pick the cable in two checks: it must carry the motor’s full-load current with a margin, and the voltage drop over the run must stay low (we use a 3% target). On copper XLPE armoured cable, 4 sq mm covers motors up to about 15 HP on runs up to 50 m; a 15 HP motor 100 m away needs 10 sq mm, and a 50 HP motor 200 m away needs 50 sq mm. On long runs, the length decides the size, not the HP.

This guide is for contractors, panel builders and site engineers wiring pumps, lifts, AHUs, chillers and compressors in hotels, factories and hydro sites around Gangtok, Rangpo, Singtam and Namchi. The same method works across North Bengal, Bihar and Sikkim.

How many amps does a 3 phase motor draw?

Always start from the nameplate. If you don’t have it yet, the BEE star-labelling schedule for induction motors gives the maximum full-load current for 4-pole energy-efficient motors made to IS 12615 (BEE Schedule 6, Table 2). These are upper limits, so a real motor usually draws a little less, which makes them safe for cable sizing.

Motor (HP / kW)Full-load current, max (A)× 1.25 margin (A)
1 HP / 0.75 kW2.22.8
2 HP / 1.5 kW3.84.8
3 HP / 2.2 kW5.16.4
5 HP / 3.7 kW8.110.1
7.5 HP / 5.5 kW11.414.3
10 HP / 7.5 kW15.419.3
15 HP / 11 kW2227.5
20 HP / 15 kW3037.5
25 HP / 18.5 kW3645
30 HP / 22 kW4354
40 HP / 30 kW5670
50 HP / 37 kW6986

The 25% margin is common trade practice for motor cables, the same margin we use in our MCCB rating guide. It also matches the rough “about 1.5 A per HP” rule in our DOL vs star delta starter guide. Submersible pump motors are built differently, so for borewells use our submersible pump cable size chart instead.

How much current can copper armoured cable carry?

KEI’s technical handbook lists these ratings for 3 core copper XLPE armoured cable, 1.1 kV (KEI Technical Handbook). Its stated conditions are 30°C ground and 40°C air.

Size (sq mm)In ground (A)In air (A)AC resistance at 90°C (Ω/km)Voltage drop, our calc (mV per A per m)
445415.908.8
656523.945.9
1074702.343.5
1695891.472.2
251221190.9311.4
351461470.6711.1
501731790.4950.8

KEI prints resistance and reactance, not a voltage drop figure. We worked out the last column from KEI’s AC resistance and reactance with the standard three-phase formula: voltage drop (V) = 1.732 × I × L × (R cos φ + X sin φ) ÷ 1000, at a running power factor of 0.85. That power factor is our assumption for a loaded motor. Other brands (Havells, Polycab, Mescab, RR Kabel) publish their own sheets, and their figures differ a little.

KEI’s list starts at 4 sq mm for this cable type. On sites, 4 sq mm is also the usual smallest armoured motor cable, because smaller cores are hard to gland and lug properly.

Cable size for 3 phase motor: chart by HP and length

This chart is our worked guide, not a maker’s table. For each size we checked two things. First, the in-air rating must be at least 1.25 × the full-load current. Second, the voltage drop at full load must be 3% or less (12.45 V on 415 V). The 3% target is general trade practice; follow your project spec if it says otherwise. Length is the one-way cable route from the starter to the motor.

Motor (DOL, 415 V)Up to 50 mUp to 100 mUp to 200 m
1–3 HP4 sq mm4 sq mm4 sq mm
5 HP4 sq mm4 sq mm6 sq mm
7.5 HP4 sq mm4 sq mm10 sq mm
10 HP4 sq mm6 sq mm10 sq mm
15 HP4 sq mm10 sq mm16 sq mm
20 HP6 sq mm10 sq mm25 sq mm
25 HP6 sq mm16 sq mm25 sq mm
30 HP10 sq mm16 sq mm25 sq mm (just inside 3%)
40 HP10 sq mm25 sq mm35 sq mm
50 HP16 sq mm25 sq mm50 sq mm

Copper XLPE armoured, 3 core, laid in air. If the cable is grouped on a tray with other cables, or laid in a pipe, the rating drops. Apply the maker’s derating factors, and go one size up when you are close to the limit.

Worked example: 15 HP pump at a hotel, 120 m from the panel

Many hill hotels pump water up from a lower tank to the roof, and the pump house can be far below the main building. Say the motor is 15 HP, three-phase, and the cable route along the slope is 120 m.

  1. Current: BEE maximum for 15 HP (11 kW) is 22 A. With 25% margin: 22 × 1.25 = 27.5 A.
  2. Current check: 4 sq mm is rated 41 A in air, so it passes on current alone.
  3. Voltage drop on 4 sq mm: 8.8 mV/A/m × 22 A × 120 m ÷ 1000 = about 23 V. That is 5.6% of 415 V. Too much.
  4. Try 6 sq mm: 5.9 × 22 × 120 ÷ 1000 = about 15.5 V, or 3.7%. Still above 3%.
  5. Try 10 sq mm: 3.5 × 22 × 120 ÷ 1000 = about 9.3 V, or 2.2%. This passes.

So the answer is 3 core × 10 sq mm copper armoured cable, even though 4 sq mm “carries the amps”. This is a common sizing mistake on long motor runs: the cable looks fine on current, but the motor runs on low voltage, draws more current and burns its winding.

At the end of a long rural or hill line the supply is often already low. In that case, go one more size up.

What cable for a star delta motor?

A star delta starter needs two 3-core runs (six cores) from the starter to the motor. Each run carries the winding current, about 58% of the line current, so contractors often size each run for that current, as our starter guide explains. On long runs, voltage drop can still decide the size, so do not cut the size just because the current is lower. Ask your designer to check both runs, or send us the details and we will work it out with you.

In general trade practice, motors above about 7.5 HP use star delta. For a 20 HP motor 100 m away on star delta, write it in the BOQ as “2 runs × 3 core × __ sq mm copper armoured”, not “6 core”.

Copper or aluminium cable for motor?

  • Copper is the usual choice up to about 16 sq mm. It is smaller for the same current, easier to bend in a crowded motor terminal box, and lugs and glands are simpler.
  • Aluminium XLPE armoured cable makes sense for big motors and long feeders, roughly 25 sq mm and above. It is lighter and costs less per metre, but it needs a bigger size for the same load. KEI lists 3 core 25 sq mm aluminium XLPE armoured at about 95 A in ground and 93 A in air, against 122 A and 119 A for copper. See our aluminium armoured cable current rating chart.
  • Use bimetallic lugs where aluminium cable meets copper motor or starter terminals.

What is different on Sikkim hill sites?

  • Measure along the route, not on the map. Cable goes down the slope, along retaining walls and round bends. Add a few metres at each end for the gland and loop.
  • Landslides and falling stones. Use armoured cable, clamp it on cleats along walls, and keep it away from drains that run full in the monsoon.
  • Industry in East Sikkim. The Department of Pharmaceuticals’ cluster survey lists Sikkim’s pharma cluster in East Sikkim. Such plants run many motors (AHUs, chillers, compressors, pumps), and the BOQ usually asks for exact cable sizes, makes and test certificates.
  • Altitude and cold. At high sites, ask the motor maker whether the motor needs derating. Cool air does not mean you can size the cable smaller; stay with the catalogue rating.
  • Lightning. Long cable runs to pump houses can pick up surges. Earth the motor body, the armour at both glands and the starter, and fit an SPD at the panel.

A heavy drum of armoured cable is hard to move on narrow hill roads, so ask for cut lengths per motor instead of full drums.

What to write in the BOQ for motor cable

ItemExample
Cable1.1 kV, copper, XLPE insulated, armoured, 3 core × 10 sq mm
StandardIS 7098 (Part 1) for XLPE
Runs1 run (DOL) or 2 runs (star delta)
LengthCut length per motor, with motor tag (P-1, AHU-2)
BrandApproved makes, e.g. Havells, Polycab, KEI, Mescab, RR Kabel
AccessoriesDouble compression glands, copper or bimetallic lugs, earth wire
ProtectionMPCB or MCCB with rating, starter type, overload range
DocumentsTest certificate, invoice with HSN and GST

The breaker or MPCB rating must not be above what the cable can carry after derating. Get all motor wiring done and tested by a licensed electrician.

Why buy motor cable from an authorised dealer?

Shree Shyam Suppliers is an authorised dealer for Havells and Mescab, and we also deal in Polycab, KEI and RR Kabel armoured cable. We cut it to the exact length per motor and supply glands and lugs on the same quote. Rates move with copper prices, so WhatsApp us for today’s rate. Browse our cables and wires.

Ordering tip

Send Shree Shyam Suppliers on WhatsApp: a list of motors with HP (or a nameplate photo), DOL or star delta, cable route length for each, laid in air, tray or ground, copper or aluminium, preferred brand, glands and lugs needed, and your site location. We will reply with a cable size for each motor and an itemised quote. For sites outside North Bengal, nearby Bihar and Sikkim, WhatsApp us your site location and we’ll tell you how we can supply.

Quick answers

Which cable size for a 10 HP 3 phase motor?

A 10 HP motor draws up to about 15.4 A. On copper armoured cable, 4 sq mm is enough up to about 50 m, 6 sq mm up to about 100 m and 10 sq mm up to about 200 m for a 3% voltage drop.

Which cable for a 5 HP 3 phase motor?

A 5 HP motor draws up to about 8.1 A, so 4 sq mm copper armoured cable is enough up to about 100 m. For runs up to about 200 m, use 6 sq mm.

How many amps does a 3 phase motor draw per HP?

At 415 V, an energy-efficient 4-pole motor draws roughly 1.4 to 1.6 A per HP; BEE lists a maximum of 15.4 A for 10 HP and 69 A for 50 HP. Always use the nameplate current for final sizing.

What cable size for a 50 HP motor?

A 50 HP motor draws up to about 69 A. On copper XLPE armoured cable, 16 sq mm suits runs up to about 50 m, 25 sq mm up to about 100 m and 50 sq mm up to about 200 m; aluminium needs a bigger size.

Is voltage drop or current more important for motor cable?

Both must pass, but on runs over about 50 to 100 m voltage drop usually decides the size. A cable that carries the amps can still starve the motor of voltage and burn the winding.